Voltage Drop and Wire Sizing Explained: A Practical Design Method
Learn how voltage, current, distance, conductor area, material, temperature, and allowable drop interact when choosing a feeder conductor.
Why this calculation matters
Wire sizing is not one calculation. A conductor can satisfy a voltage-drop target and still be unacceptable for ampacity, temperature, short-circuit withstand, mechanical strength, or terminal compatibility.
A useful early design method is to separate electrical loss from regulatory ampacity: first calculate resistance and drop, then apply the installation-specific current-carrying and protection requirements.
What you will calculate
- Relate conductor area to resistance and voltage drop.
- Understand why low-voltage systems are especially sensitive to feeder drop.
- Compare percentage-drop and power-loss criteria.
- Avoid using a voltage-drop result as a code-compliance claim.
Given values
- 24 V DC source
- 25 A load
- 8 m one-way copper run
- Target maximum feeder drop: 3%
- Candidate conductor area: 8.37 mm², approximately 8 AWG
- Copper resistivity for the screening calculation: 0.01724 Ω·mm²/m at 20 °C
Governing equations
Conductor resistance
R = ρL / AResistance is proportional to length and inversely proportional to conductor area.
DC loop drop
ΔV = I ρ(2L) / AThe factor of two accounts for the outbound and return conductors.
Percent voltage drop
Drop % = 100 ΔV / VsourceA fixed absolute drop is more serious on a lower-voltage bus.
Minimum area from a drop target
Amin = I ρ(2L) / ΔVmaxThis rearrangement gives a first-pass conductor area before selecting a standard size.
Worked solution
1. Convert the drop target to volts
A 3% target on a 24 V bus corresponds to only 0.72 V. This illustrates why low-voltage DC distribution often becomes conductor-heavy.
ΔVmax = 0.03 × 24 = 0.72 V2. Estimate the minimum copper area
Using a 16 m loop length and the room-temperature copper resistivity gives a theoretical area of about 9.58 mm². That falls between common AWG sizes, so the next larger standard conductor should be evaluated.
Amin ≈ 25 × 0.01724 × 16 / 0.72 = 9.58 mm²3. Test the 8 AWG candidate
An 8.37 mm² conductor is smaller than the calculated 9.58 mm² target, so it should fail the 3% drop target. The calculation confirms roughly 0.824 V drop, or 3.43%.
Rloop ≈ 0.01724 × 16 / 8.37 = 0.03296 Ω; ΔV ≈ 0.824 V; drop ≈ 3.43%4. Move to the next larger conductor
A 6 AWG conductor is approximately 13.3 mm². Repeating the same calculation gives roughly 0.519 V, or 2.16%, before temperature correction and connection losses.
ΔV6AWG ≈ 25 × 0.01724 × 16 / 13.3 = 0.519 V ≈ 2.16%Engineering interpretation
For the stated 24 V, 25 A, 8 m run, 8 AWG does not meet the 3% screening target while 6 AWG does at the reference temperature.
The choice of 6 AWG is still provisional until ampacity, installation temperature, bundling, terminal ratings, fault protection, and local code requirements are checked.
Sanity checks
- At the same current and length, halving conductor area should approximately double voltage drop.
- At the same power, increasing system voltage reduces current and therefore reduces feeder loss dramatically.
- Temperature correction should never make copper resistance decrease as the conductor gets hotter.
Common mistakes
- Selecting wire only from an ampacity table and ignoring voltage drop.
- Selecting wire only from voltage drop and ignoring ampacity.
- Mixing feet, meters, circular mils, and mm² without explicit conversion.
- Forgetting that three-phase voltage-drop equations differ from two-wire DC or single-phase calculations.
References and model boundaries
- Use current conductor-resistance data and the applicable electrical code for the installation.
- Voltage-drop targets are design criteria; mandatory requirements depend on jurisdiction and application.
For safety-critical, regulated, production, or otherwise consequential work, independently verify the result using the governing standard, current manufacturer data, and qualified engineering review. See the site methodology and engineering disclaimer.