Electrical Engineering · Worked example

Voltage Drop and Wire Sizing Explained: A Practical Design Method

Learn how voltage, current, distance, conductor area, material, temperature, and allowable drop interact when choosing a feeder conductor.

By 8 minute readPublished 2026-08-11Reviewed 2026-08-11

Why this calculation matters

Wire sizing is not one calculation. A conductor can satisfy a voltage-drop target and still be unacceptable for ampacity, temperature, short-circuit withstand, mechanical strength, or terminal compatibility.

A useful early design method is to separate electrical loss from regulatory ampacity: first calculate resistance and drop, then apply the installation-specific current-carrying and protection requirements.

What you will calculate

  • Relate conductor area to resistance and voltage drop.
  • Understand why low-voltage systems are especially sensitive to feeder drop.
  • Compare percentage-drop and power-loss criteria.
  • Avoid using a voltage-drop result as a code-compliance claim.

Given values

  • 24 V DC source
  • 25 A load
  • 8 m one-way copper run
  • Target maximum feeder drop: 3%
  • Candidate conductor area: 8.37 mm², approximately 8 AWG
  • Copper resistivity for the screening calculation: 0.01724 Ω·mm²/m at 20 °C

Governing equations

Conductor resistance

R = ρL / A

Resistance is proportional to length and inversely proportional to conductor area.

DC loop drop

ΔV = I ρ(2L) / A

The factor of two accounts for the outbound and return conductors.

Percent voltage drop

Drop % = 100 ΔV / Vsource

A fixed absolute drop is more serious on a lower-voltage bus.

Minimum area from a drop target

Amin = I ρ(2L) / ΔVmax

This rearrangement gives a first-pass conductor area before selecting a standard size.

Worked solution

1. Convert the drop target to volts

A 3% target on a 24 V bus corresponds to only 0.72 V. This illustrates why low-voltage DC distribution often becomes conductor-heavy.

ΔVmax = 0.03 × 24 = 0.72 V

2. Estimate the minimum copper area

Using a 16 m loop length and the room-temperature copper resistivity gives a theoretical area of about 9.58 mm². That falls between common AWG sizes, so the next larger standard conductor should be evaluated.

Amin ≈ 25 × 0.01724 × 16 / 0.72 = 9.58 mm²

3. Test the 8 AWG candidate

An 8.37 mm² conductor is smaller than the calculated 9.58 mm² target, so it should fail the 3% drop target. The calculation confirms roughly 0.824 V drop, or 3.43%.

Rloop ≈ 0.01724 × 16 / 8.37 = 0.03296 Ω; ΔV ≈ 0.824 V; drop ≈ 3.43%

4. Move to the next larger conductor

A 6 AWG conductor is approximately 13.3 mm². Repeating the same calculation gives roughly 0.519 V, or 2.16%, before temperature correction and connection losses.

ΔV6AWG ≈ 25 × 0.01724 × 16 / 13.3 = 0.519 V ≈ 2.16%
Result

Engineering interpretation

For the stated 24 V, 25 A, 8 m run, 8 AWG does not meet the 3% screening target while 6 AWG does at the reference temperature.

The choice of 6 AWG is still provisional until ampacity, installation temperature, bundling, terminal ratings, fault protection, and local code requirements are checked.

Sanity checks

  • At the same current and length, halving conductor area should approximately double voltage drop.
  • At the same power, increasing system voltage reduces current and therefore reduces feeder loss dramatically.
  • Temperature correction should never make copper resistance decrease as the conductor gets hotter.

Common mistakes

  • Selecting wire only from an ampacity table and ignoring voltage drop.
  • Selecting wire only from voltage drop and ignoring ampacity.
  • Mixing feet, meters, circular mils, and mm² without explicit conversion.
  • Forgetting that three-phase voltage-drop equations differ from two-wire DC or single-phase calculations.

References and model boundaries

  • Use current conductor-resistance data and the applicable electrical code for the installation.
  • Voltage-drop targets are design criteria; mandatory requirements depend on jurisdiction and application.

For safety-critical, regulated, production, or otherwise consequential work, independently verify the result using the governing standard, current manufacturer data, and qualified engineering review. See the site methodology and engineering disclaimer.